32062: Timeout sending a Write Request telegram (network error ?)

Info:
Data type:

Description:
To transfer a parameter value to the ACOPOS, the NC manager first sends a write-request telegram from the PLC to the ACOPOS. This error is displayed if the NC manager detects that the corresponding CAN telegram has not yet been transferred to the CAN bus 70ms after the corresponding CAN send function call is made.

Reaction:
Resets the interface of the corresponding CAN write channel.

Cause/Remedy:
None of the CAN nodes connected to the PLC CAN interface is active in the CAN communication so that the CAN bus acknowledge does not occur after sending the CAN telegram.
Network connection interruption or failure of all ACOPOS devices.
See also error number 1004.