Description:
Runtime error during active network life sign monitoring, if no cyclic telegram arrives for a specified amount of time (NETWORK_LIVE_CTRL).
See also error number 4005.
Reaction:
See error number 9000.
All digital outputs (AC130, AC131) are deactivated, (i.e. the output levels are set to LOW and all switchable IOs are set to input).
A movement of the virtual axis is aborted.
Cause/Remedy:
Problem in network life sign monitor:
Time for network life sign monitoring NETWORK_LIVE_CTRL is defined too short.
Network life sign monitoring is activated too early, before cyclic telegrams are sent.
Problem in network data transfer:
Cycle time exceeded, extremely high computing time load or failure of the controller CPU.
Disturbance or disconnection of the network connection. See wiring guidelines error number 7030.
The network load is too high.