32020: System module data could not be read from the drive during NC manager INIT

Info:
Data type:

Description:
A system module should only then be transferred to the ACOPOS during the system module download function, if it is not already present on the ACOPOS. To detect this, the NC manager reads the version data of the system modules which are stored on the ACOPOS (ACOPOS BsLoader and ACOPOS operating system) during the ACOPOS startup function. This error number is output if an error occurs with this procedure. In addition, further details are also output about the error which occurred.

Reaction:
Transfer of the system module to the ACOPOS is aborted.

Cause/Remedy:
Overload, malfunction or interruption of the network connection or ACOPOS failure.
See also error number 1004.
See also error number 1012.