7219: DC bus: Charging: Voltage too low

Info: Minimum required DC bus voltage
Data type: REAL

Description:
Runtime error using the 'switch on controller' command.
The main relay is open.
UDC_FILTER < 0.9*UDC_NOMINAL
The filtered DC bus voltage UDC_FILTER is smaller than the tolerated by 10% nominal voltage 0.9*UDC_NOMINAL.

Reaction:
See error number 7210.

Cause/Remedy:
See Power transmission

Invalid mains: Supply voltage or DC bus voltage is too low. -> Check the DC bus voltage.
Incorrect configuration of the nominal voltage initialization: UDC_NOMINAL too high.