7029: Encoder: Incremental signal amplitude too small

Info: Slot
Data type: USINT

Description:
Runtime error in an encoder with activated monitor (activation, see error number 7030). The amplitude of the sinusoidal AB signals is smaller than 17.5% (AC120) or 20.0% (AC121) of the maximum amplitude which can be displayed (see ACOPOS user's manual).

Reaction:
See error number 7030.

Cause/Remedy:
No encoder supply or supply contains an error.