37103: Slave trigger outside of window

Info:
Data type:

Description:
Runtime error when cam automat is active (CMD_CAM_START) if a slave trigger is reached outside the valid window position (CAM_SL_TRIG_WINDOW).

Reaction:
No effect when 'real' false trigger occurs.
If a label trigger is rejected, the expected value is still set to the slave interval defined in the parameter. This could result in a deviation.

Cause/Remedy:
Window defined too small.
The first trigger reached was false or label tape not correctly setup before the start.
The defined slave interval (CAM_SL_S_SYNC + CAM_SL_S_COMP) deviates too strongly from the actual interval.
Interval jump in the label tape (bonding point).
'Real' false trigger -> Check trigger sensor.
Error analysis with CAM_SL_TRIG_IV_MIN, CAM_SL_TRIG_IV_MAX.